Napoleon · Gas fireplace troubleshooting

Pilot will not stay lit - direct vent

What is going on

Pilot lights but won't hold when you let go of the knob. On a direct-vent Napoleon with a thermocouple, that's most often a thermocouple not making enough millivolts, or a valve magnet that won't hold. A dirty tip or a loose connection is the cheap fix, so start there. The service flowchart also covers the GD70NT-S and GD70PT-S.

Likely causes

  • Loose thermocouple at the valve
  • Dirty thermocouple tip not fully in the flame
  • Low thermocouple output
  • Weak valve magnet coil
  • Undersized gas supply line

Check in this order

  1. Tighten the thermocouple at the valve, snug only, because a loose nut gives a weak reading
  2. Clean any buildup off the thermocouple tip so it sits fully in the flame
  3. Measure thermocouple millivolts (spec 20-30 mV open circuit, 10-15 mV closed circuit), low open circuit means replace the thermocouple
  4. Test the valve magnet coil (Robertshaw 9-11 ohms; SIT 820 Nova: hold-in test)
  5. Check the supply line size against local code and replace if undersized
  6. With a fresh thermocouple and a good coil, look at pilot flame size and shape
  7. Gas work and valve replacement belong to a licensed technician

Applies to: Napoleon direct-vent gas fireplaces (general service manual flowchart; applies to GD70NT-S/GD70PT-S)

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 1-3 Troubleshooting, Pilot Not Holding Flowchart, p.2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.