Majestic · Gas fireplace troubleshooting

Millivolt: pilot will not light with the piezo

DVBL7 Millivolt

What is going on

Repeated clicks of the piezo igniter and no pilot flame.

Likely causes

  • Igniter wire off
  • Bad igniter or pilot assembly
  • No gas or low gas pressure
  • Propane tank empty

Check in this order

  1. Open the door and make sure the igniter wire is connected
  2. Look for a spark at the electrode and pilot; no spark with wire good means replace the pilot assembly
  3. Check the shutoff valve; bent, restricted or undersized lines give low pressure
  4. Check the propane tank level

Applies to: 400DVBLN/PV7, 500DVBLN/PV7 (millivolt)

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Majestic DVBL7 Series Installation and Operating Instructions, p. 46. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.