Majestic · Gas fireplace troubleshooting
Millivolt: pilot lights but will not stay lit
What is going on
Pilot burns while the knob is held in but goes out when released.
Likely causes
- Weak thermocouple
- Bad gas valve
Check in this order
- Make sure the flame wraps the thermocouple; clean or adjust the pilot
- Check thermocouple is fully inserted and tight at the valve
- Disconnect the thermocouple, meter its tip to the copper lead with the pilot running and the knob held in: below 15 mV replace the pilot assembly
- Above 15 mV and still dropping out replace the valve
Applies to: 400DVBLN/PV7, 500DVBLN/PV7 (millivolt)
More gas fireplace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Majestic DVBL7 Series Installation and Operating Instructions, p. 46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.