Napoleon · Gas fireplace troubleshooting

Pilot lit, no gas to main burner (knob on HI, switch/thermostat ON)

What is going on

Pilot burning, knob on HI, wall switch or thermostat on, and no main flame. Gas valve isn't opening or the call isn't reaching it. Napoleon GD70 STARfire. Work from the wall switch back to the valve, then the burner.

Likely causes

  • Defective thermostat or wall switch
  • Defective switch wiring
  • Plugged main burner orifice
  • Faulty valve

Check in this order

  1. Meter across the wall switch or thermostat terminals with it turned on, it should read close to 0 V and show continuity, if not, replace the switch or thermostat
  2. Disconnect the switch wires at the valve and check continuity of the field wiring run, an open or high resistance reading means the field wires are bad; repair or replace them
  3. With the switch calling, meter the valve terminals 1 and 3 for the control voltage the manual lists, voltage present and no flow points at the valve
  4. If the valve gets voltage and the burner still does not light, check and clear the main burner orifice
  5. If the orifice is clear, replace the gas valve
  6. Leak test all gas joints with approved solution after any gas side work, and use a licensed gas technician for the valve

Applies to: Napoleon GD70 STARfire direct-vent fireplace (GD70NT-S natural gas, GD70PT-S propane)

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Napoleon GD70NT-S / GD70PT-S Installation & Operating Instructions W415-0434, Troubleshooting table, p.26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.