DSI fireplace: burner lights but will not stay lit
What is going on
The burner lights and then goes out because the module does not prove flame (flame rectification).
Likely causes
- Reversed polarity at the junction box
- Junction box, module or burner not grounded
- Ignitor / flame sensor not in the flame
- Loose ignitor cable or flame sensor wire
- Flame too close to the ceramic insulator
- Open high-temperature limit (Fenwal units with one)
- Grate not installed (CFX-DA)
Check in this order
- Warning: Disconnect 110/120 VAC before changing wiring.
- Check polarity meter from 120 VAC HOT on the module to ground should read 110/120 VAC; from 120 VAC RTN to ground should read 0 V. If reversed, shut off power and swap hot and neutral at the junction box.
- The junction box must be grounded, and the module/burner ground must be secure; ground leads must have no paint, oil or other insulation under them. The system works by flame rectification, which needs a good ground.
- Adjust the bracket so the probe stays in the flame whenever the burner is lit. Flame too close to the ceramic insulator causes nuisance lockouts and electrode failure.
- Check the ignitor cable connection. Fenwal: the yellow flame sensor wire must be on S1 at the module.
- CFX-DA the grate must be installed for the unit to work correctly.
- RAM-1-RS if polarity, grounding and probe position are all correct, replace the module.
Applies to: Heat-N-Glo DSI fireplaces: RAM 1MC1-01/-05, RAM-1-RS, Fenwal 24 VAC, CFX-DA, Grand-50-C
More gas fireplace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Heat-N-Glo DSI / HSI Troubleshooting Guide (Professional Development), p.11, 18, 24, 30, 37-38, 45. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.