Heat & Glo · Gas fireplace troubleshooting

HSI fireplace: ignitor glows but no flame

What is going on

The hot surface ignitor heats up but the burner does not light.

Likely causes

  • No 24 VAC reaching the module or gas control
  • Open high-temperature limit or glass microswitch not pressed
  • Gas control (valve) not opening
  • Wiring fault

Check in this order

  1. With the rocker ON 110/120 VAC at transformer terminals 1 and 3 (if not, check REM, breaker and wiring), and 24 VAC at terminals 4 and 5 (if not, replace the transformer).
  2. Check 24 VAC between 24 V and 24 V GND on the module. If missing, test the high-temperature limit (normally closed, must have continuity) and make sure the glass microswitch is pressed in.
  3. Check every wire connection, then check for 24 VAC at the gas control. With 24 VAC present and no gas flow, the gas control is the next suspect; confirm gas supply and pressure before replacing it.

Applies to: Heat-N-Glo HSI fireplaces

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Heat-N-Glo DSI / HSI Troubleshooting Guide (Professional Development), Section 7 HSI, p.53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.