Heat & Glo · Gas fireplace troubleshooting
HSI fireplace: hot surface ignitor will not glow
What is going on
Heat-N-Glo hot surface ignition fireplace: the ignitor does not heat up. It will not glow without 24 VAC on the 24 V side of the module.
Likely causes
- No 110/120 VAC at REM or at transformer terminals 1 and 3
- Failed transformer (no 24 VAC at terminals 4 and 5)
- Open high-temperature limit switch
- Glass microswitch not pressed in (units with one)
- Failed hot surface ignitor
- Wiring fault
Check in this order
- Turn the On/Off rocker ON. Confirm 110/120 VAC at REM on the junction box and at L1/L2 on the module.
- Transformer 110/120 VAC at terminals 1 and 3, 24 VAC at terminals 4 and 5. Primary OK but no 24 VAC = replace the transformer.
- Module 24 VAC between 24 V and 24 V GND. Missing = check the high-temperature limit (normally closed on HSI units; no continuity = replace it) and make sure the glass microswitch is pressed in, since it only passes current when depressed.
- Check for 110/120 VAC at the ignitor connectors. If voltage is there, replace the ignitor.
- Measure ignitor resistance 45-400 ohms is good; outside that range, replace the ignitor.
Applies to: Heat-N-Glo HSI (hot surface ignition) fireplaces, Honeywell valve
More gas fireplace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Heat-N-Glo DSI / HSI Troubleshooting Guide (Professional Development), Section 7 HSI, p.47-52. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.