HSI fireplace: flame comes on but will not stay lit

What is going on

Before you start, make sure the gas is off and the unit is cool, and turn the power off before opening any junction box. On a Heat-N-Glo hot surface ignition fireplace, the burner lights off the ignitor and then drops out. With these systems the module has to prove flame through the ignitor and sensor, and it only does that if it has a clean ground and correct polarity. A reversed hot and neutral or a missing ground at the junction box will make the flame signal unreliable. The ignitor sitting out of the flame can do the same thing, so check all three before you replace any parts.

Likely causes

  • Junction box or module not grounded
  • Reversed polarity on the 120 VAC supply
  • Ignitor or sensor not sitting in the flame
  • Loose connections at the module harness

Check in this order

  1. With power off, confirm the junction box and the module both have a solid ground and ground them if either is not
  2. Check polarity with power on and the meter set to AC volts: 120 VAC HOT on the module to ground should read 110/120 VAC, and 120 VAC RTN to ground should read 0 V
  3. If polarity is reversed, shut off power and swap hot and neutral at the junction box, line voltage work is for a qualified electrician or licensed tech
  4. Look at the flame pattern and reposition the ignitor bracket so the ignitor sits in the flames over the port holes
  5. Check the harness connections at the module and the ignitor are tight and clean
  6. Relight and watch a full cycle to confirm the flame now stays on

Applies to: Heat-N-Glo HSI fireplaces

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Heat-N-Glo DSI / HSI Troubleshooting Guide (Professional Development), Section 7 HSI, p.54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.