Napoleon · Gas fireplace troubleshooting

Main burner goes out and pilot goes out

What is going on

So the main burner and the pilot both go out on you? On the Napoleon GD70 STARfire, that tells you it's most likely a venting issue. If it were just a gas valve problem the pilot would normally stay lit. When exhaust cycles back into the intake the flames get starved and snuff out. Don't keep relighting it over and over. Check the vent first, and once that's sorted, move on to the 'Main burner goes out; pilot stays on' checks.

Likely causes

  • Blocked vent
  • Flue gases recirculating because of poor joint seals or a poor installation
  • 4" flex vent disconnected from the fireplace
  • Blocked or iced terminal in cold weather

Check in this order

  1. Treat it as a venting fault and do not keep relighting until the vent is checked
  2. Check the vent system for blockage at the terminal and along the pipe
  3. Check all vent joint seals and the installation for recirculation of exhaust into the intake
  4. Make sure the 4" flexible vent is still attached to the fireplace, and re-attach it if disconnected
  5. After the vent is confirmed good, relight and let it run through a full cycle
  6. Then run the 'Main burner goes out; pilot stays on' checks
  7. If the problem repeats, get a licensed gas technician to look at the vent installation

Applies to: Napoleon GD70 STARfire direct-vent fireplace (GD70NT-S natural gas, GD70PT-S propane)

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Napoleon GD70NT-S / GD70PT-S Installation & Operating Instructions W415-0434, Troubleshooting table, p.26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.