SIT 820 Nova millivolt valve: pilot will not stay lit
What is going on
The pilot lights while the knob is held but goes out when released, or drops out later.
Likely causes
- Wrong inlet pressure
- Pilot flame too small or not on the thermocouple/thermopile
- Thermocouple or thermopile not fully seated, dirty or failed
- Failed safety magnet in the valve
- Wrong or blocked pilot orifice
Check in this order
- Relight and hold the knob in for 30 seconds before releasing.
- Check the thermocouple and thermo-generator are fully inserted in the pilot; thermocouple tight in the valve = hand tight plus 1/4 turn with a wrench. Clean the tips (upper 3/8 in.) with very fine emery cloth.
- Millivolt Plus open-circuit thermocouple voltage should be 18-28 mV; under 14 mV = replace the thermocouple.
- Safety magnet (mV Plus) hold the pilot button, reconnect the thermocouple, measure between the solder button on the magnet and the valve body. Above 6 mV (vented) or 8.5 mV (unvented) and the magnet will not hold = replace the valve. Closed-circuit reading equal to open-circuit = open coil, replace the valve.
- Millivolt system remove the operator wires and measure TPTH to TP; above 110 mV and the magnet will not hold = replace the valve.
- Replace a blocked or wrong pilot orifice with the exact one for the appliance and gas type.
Applies to: Fireplaces and gas logs with SIT 820 Nova MV / Millivolt Plus valves
More gas fireplace guides
- Flameworks millivolt valve: pilot outage or burner will not come on
- Maxitrol GV60 remote valve: fireplace will not light or respond
- Proflame (SIT DFC): fan, AUX outlet, split flow or OFF command not working
- Proflame (SIT DFC): pilot lights but main burner will not light or drops out
- Proflame (SIT DFC): pilot will not light or DFC locks out
- SIT 820 Nova millivolt valve: main burner will not come on or will not cycle
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SIT 820 Nova MV Troubleshooting Guide; SIT Gas Control Valve troubleshooting flow chart (Fireparts). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.