Napoleon · Gas fireplace troubleshooting
Main burner will not light - natural vent
What is going on
Pilot is on but main burner will not fire on a natural-vent unit.
Likely causes
- Pilot too small to reach burner ports
- Low thermopile output
- Low supply pressure
- Spill or vent safety switch open
- Blocked burner/orifice
- No switch on terminals 1 & 3
- Faulty switch/wiring
- Bad operator coil
Check in this order
- Check pilot size and position - it must reach the ignition ports.
- Test thermopile millivolts and confirm it is connected.
- Test inline supply pressure.
- Test spill and vent safety switches for function and connection.
- Check and clean burner and orifice.
- Confirm a switch or remote is on terminals 1 & 3; jumper 1 & 3 to test - if the burner lights, the switch/wiring is at fault.
- If not, test the operator coil and replace the valve if out of spec.
Applies to: Napoleon natural-vent (B-vent) gas fireplaces with spill switch (general service manual flowchart)
More gas fireplace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 1-3 Troubleshooting, Main Burner Not Lighting Flowchart, p.13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.