Napoleon · Gas fireplace troubleshooting

Test: door gasket seal (paper test)

What is going on

This is the old paper test for a door gasket on Napoleon gas fireplaces, direct vent, natural vent or vent-free. What I usually find on a call-back is a gasket that has flattened out or a latch that has loosened up, and the paper shows it in about a minute. A leaky door on a direct vent unit upsets combustion air balance and can let products of combustion into the room, so it is worth doing right.

Likely causes

  • Worn or damaged door gasket
  • Latch worn or out of adjustment so the door does not pull tight

Check in this order

  1. Cut a strip of paper about 1" x 6" and place it between the door and the fireplace body, then close and latch the door.
  2. Pull the paper out. If it tears rather than slipping out, the seal is good there; if it slides out, inspect the door, gasket and latch.
  3. Repeat at several positions around the frame, not just one spot.
  4. Look for an even colour line on the firebox opening where the gasket presses; it should not extend past the gasket perimeter.
  5. Replace a hardened or crushed gasket and adjust or replace the latch before putting the unit back in service

Applies to: Napoleon gas fireplaces - direct vent, natural vent and vent-free (general service manual)

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 5 Testing & Adjustments, Testing: Gasket, p.32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.