Napoleon · Gas fireplace troubleshooting

Pilot will not stay lit - natural vent

What is going on

On a Napoleon natural-vent (B-vent) fireplace, the usual thing I find when the pilot won't hold is a weak thermocouple or thermopile signal, or a spill switch that has opened up. People forget the spill switch is wired into the same circuit, so a loose spade connector there kills the pilot just like a bad thermocouple does. Before replacing parts, check connections and the millivolt readings. A blocked pilot tube or an undersized gas line is the next likely candidate.

Likely causes

  • Loose thermocouple or thermopile connection
  • Low millivolt output
  • Blocked pilot tube or orifice
  • Undersized supply line
  • Spill switch disconnected or open, which is a vent safety and must be found, not bypassed
  • Weak magnet coil in the valve

Check in this order

  1. Check and tighten thermocouple and thermopile connections at the valve
  2. Test millivolt output (thermocouple 20-30 mV open / 10-15 mV closed; thermopile 500 mV open / min 150 mV closed), low readings mean replace the part
  3. Remove and clean the pilot tube and orifice, a spider web or lint can restrict it
  4. Confirm supply line size meets local code
  5. Verify the spill switch is connected and has continuity with the meter, and if it reads open treat it as a possible venting problem and find out why before going on
  6. Test the valve magnet coil
  7. Work on the gas side belongs to a licensed technician

Applies to: Napoleon natural-vent (B-vent) gas fireplaces with spill switch (general service manual flowchart)

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 1-3 Troubleshooting, Pilot Not Holding Flowchart, p.11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.