Napoleon · Gas fireplace troubleshooting

Pilot drops out during operation - direct vent

What is going on

Pilot lights fine, then drops out once the unit is running. Direct-vent Napoleon, GD70NT-S and GD70PT-S included. Usually the pilot is sitting wrong, or the gas pressure sags when the main burner kicks in. Check the pilot first. Then pressure. Then vent and logs.

Likely causes

  • Wrong pilot flame size or position
  • Pressure drop when burner comes on
  • Low thermocouple output
  • Weak magnet coil
  • Venting problem
  • Logs out of place

Check in this order

  1. Check pilot flame pattern, size and position, it must properly heat the thermocouple
  2. If the pilot shrinks when the burner comes on, check for pressure drop on activation, that is a supply problem
  3. Test thermocouple millivolts (20-30 mV open, 10-15 mV closed)
  4. Test the magnet coil
  5. Inspect the vent system (see Complete Unit Shutdown guide)
  6. Check log positions, misplaced logs disturb airflow and make the pilot erratic
  7. If the supply pressure is the issue, a licensed gas technician should sort out the piping

Applies to: Napoleon direct-vent gas fireplaces (general service manual flowchart; applies to GD70NT-S/GD70PT-S)

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 1-3 Troubleshooting, Pilot Failure Flowchart, p.3. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.