Goodman furnace error codes
131 codes (79 faults, 52 normal display and menu codes), plus 4 settings tables.
| Code | Meaning | Severity / type |
|---|---|---|
| 1 flash | Lockout - three failed ignition tries | High |
| 1AC | Cooling, low stage | Normal status |
| 2 flashes | Pressure switch stuck closed | High |
| 2AC | Cooling, high stage | Normal status |
| 3 flashes | Pressure switch stuck open | High |
| 4 flashes | Primary or auxiliary limit open | High |
| 5 flashes | Flame sensed with no call for heat | Critical |
| 6 flashes | Rollout limit open or control fuse blown | High |
| 7 flashes | Low flame signal | Medium |
| 8 flashes | Igniter relay fault | High |
| 9 flashes | Twinning fault | Medium |
| 10 flashes | Open fuse - no 24 V at the control | Medium |
| 11 flashes | Igniter open | High |
| 12 flashes | Inducer relay fault | High |
| 88 | Power-up self check | Normal status |
| AC1 | Cooling, low stage (communicating) | Normal status |
| AC2 | Cooling, high stage (communicating) | Normal status |
| b0 | Blower motor not running | High |
| b1 | Lost communication with blower motor | High |
| b2 | Blower motor size does not match model data | Medium |
| b3 | Blower motor limiting (power, temperature or speed) | Medium |
| b4 | Blower motor trip (lost rotor control or high current) | High |
| b5 | Blower motor locked rotor | High |
| b6 | Blower motor over/under voltage or over temperature | High |
| b7 | Blower motor missing parameters | Medium |
| b9 | Low indoor airflow | Medium |
| C1 | Low-stage cooling | Normal status |
| C2 | High-stage cooling | Normal status |
| d0 | No shared data on the control | High |
| d4 | Memory card data rejected | Medium |
| dF1 | Defrost, low-stage gas heat | Normal status |
| dF2 | Defrost, high-stage gas heat | Normal status |
| E0 | Lockout - ignition failed 3 times | High |
| E1 | Low-stage pressure switch closed at start of heat | Medium |
| E2 | Low-stage pressure switch will not close | High |
| E3 | High limit or rollout limit open | High |
| E4 | Flame sensed with no call for heat | Critical |
| E5 | Control fuse open | Medium |
| E6 | Low flame signal | Low |
| E7 | Igniter circuit fault | High |
| E8 | High-stage pressure switch closed at start of heat | Medium |
| E9 | High-stage pressure switch will not close | Medium |
| E10 | Grounding fault / poor neutral connection | High |
| E11 | Flame rollout switch open | Critical |
| E12 | Redundant relay open | High |
| E13 | Redundant relay stuck closed | High |
| Eb0 | Blower motor not running | High |
| Eb1 | Lost communication with blower motor | High |
| Eb2 | Blower motor hp does not match model data | Medium |
| Eb3 | Blower motor running in power, temperature or speed limit | Medium |
| Eb4 | Blower motor current trip or lost rotor control | High |
| Eb5 | Blower motor locked rotor | High |
| Eb7 | Blower motor missing parameters | High |
| Eb9 | Inadequate airflow | Medium |
| Ec1 | Network communication alarm | Medium |
| Ec2 | E-module network communication alarm | Medium |
| Ec3 | Bluetooth module network communication alarm | Low |
| Ed0 | No shared data on the network | Medium |
| Ed1 | Invalid data on network | Medium |
| Ed4 | Memory card data rejected | Medium |
| Ed5 | Invalid downloaded firmware | Medium |
| Ed6 | Unrecognized data ID | Medium |
| EE0 | Lockout - too many ignition retries (3) | High |
| EE1 | Pressure switch closed at start of heating cycle | Medium |
| EE2 | Pressure switch did not close (inducer runs, no ignition) | Medium |
| EE3 | High (primary) limit open | High |
| EE4 | Flame sensed with no call for heat | Critical |
| EE5 | Open fuse (short in low voltage wiring) | Medium |
| EE6 | Low flame signal | Low |
| EE8 | High-stage pressure switch closed at start of heating cycle | Medium |
| EE9 | High-stage pressure switch did not close | Medium |
| gH1 | Gas heat, low stage | Normal status |
| gH2 | Gas heat, high stage | Normal status |
| HP1 | Heat pump heat, low stage | Normal status |
| HP2 | Heat pump heat, high stage | Normal status |
| L0 | Low-stage heat | Normal status |
| L6F | Last 6 faults (view and clear) | Menu / mode display |
| SH1 | Special heat relay 1 | Normal status |
| SH2 | Special heat relay 2 | Normal status |
| AC | Cooling, single stage | Normal status |
| Axx | Airflow readout | Normal status |
| CFM readout | Airflow number (CFM / 100) | Menu / mode display |
| CFS | Comfort setting | Menu / mode display |
| Cr | Code release number | Menu / mode display |
| EA | 115 V polarity reversed | High |
| EEA | Reversed line polarity or grounding error | High |
| EEC | Internal gas valve error - valve energized when it should not be | Critical |
| EEE | Internal control fault (IRQ loss) | High |
| EEF | Condensate switch open | Medium |
| EEH | Twinning error | Low |
| EEJ | Inducer relay error | High |
| EEL | Igniter relay / igniter circuit fault | High |
| EEb | External gas valve error - valve not energized when it should be | High |
| EEd | Condensate or auxiliary alarm switch open | Medium |
| EEn | Igniter open | High |
| EOL | OEM test mode | Menu / mode display |
| Err | Active alarm menu | Menu / mode display |
| F | Continuous fan | Normal status |
| FAn | Continuous fan | Normal status |
| HEd | Humidifier enable | Menu / mode display |
| HI | High-stage heat | Normal status |
| HP | Heat pump heat, single stage | Normal status |
| HUd | Humidifier on | Normal status |
| IdL | Idle - no call | Normal status |
| LED off | No LED - no power or control failure | High |
| LED steady on | Normal operation | Normal status |
| Lrn | Learn menu | Menu / mode display |
| OP | Normal - waiting for a call | Normal status |
| Rapid flash | Reversed polarity | High |
| Red LED 1 flash | Red communications LED 1 flash - communication failure | Medium |
| Red LED 2 flashes | Red communications LED 2 flashes - reset in progress | Menu / mode display |
| Red LED off | Red communications LED off - normal | Normal status |
| Rx LED 1 steady flash | Green receive LED single steady flash - no network found | Low |
| Rx LED off | Green receive LED off - no power or communications error | Medium |
| Rx LED on solid | Green receive LED on solid - data lines miswired or shorted | Medium |
| Rx LED rapid flash | Green receive LED rapid flashing - normal network traffic | Normal status |
| Sr | Shared data revision | Menu / mode display |
| dHL | Dehumidify logic input level | Menu / mode display |
| dHU | Dehumidifier on | Normal status |
| gAF | Gas heat airflow | Menu / mode display |
| gFd | Gas heat fan off delay | Menu / mode display |
| gH | Gas heat, single stage | Normal status |
| gPt | Gas pressure test | Menu / mode display |
| gSt | Gas heat stage multiplier | Menu / mode display |
| gbP | Backup heat balance points | Menu / mode display |
| gnd | Gas heat fan on delay | Menu / mode display |
| gtF | Gas heat trim factor | Menu / mode display |
| rFd | Reset to factory defaults | Menu / mode display |
| uAC | Inverter cooling | Normal status |
| uHP | Inverter heat pump heat | Normal status |
| utL | Ventilator on | Normal status |
Settings and specs
Normal status displays (7-segment)
Installer menu · Goodman/Amana GM9S96/AM9S96
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat (single stage) | gH |
| Factory (OEM) test mode | EOL |
- These are normal operating displays, not fault codes.
Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Status Codes - Status Menu p.28
Normal status displays (7-segment)
Installer menu · Goodman/Amana GM9S80/AM9S80
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat (single stage) | gH |
| Factory (OEM) test mode | EOL |
- These are normal operating displays, not fault codes.
Source: Goodman RS6621008r2 (GM9S80 service), 1 Stage Status Codes - Status Menu p.31
Normal status displays (7-segment)
Installer menu · Goodman/Amana GM9C96/AM9C96
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
- These are normal operating displays, not fault codes.
Source: Goodman RS6612020r1 (GM9C96 service), 2 Stage Status Codes p.34
Minimum recommended filter size
Filters · Goodman/Amana GM9C96/AM9C96
| Configuration | Size code | Minimum filter |
|---|---|---|
| Upflow | *0403A* | 1 - 16 x 25 side or 1 - 14 x 24 bottom return |
| Upflow | *0603A* | 1 - 16 x 25 side or 14 x 24 bottom return |
| Upflow | *0603B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0803B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0804B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0804C* | 1 - 16 x 25 side or bottom return |
| Upflow | *0805C* | 1 - 16 x 25 side or bottom return (see note 1) |
| Upflow | *0805D* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return (see note 1) |
| Upflow | *1004C* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return |
| Upflow | *1005C* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return |
| Upflow | *1205D* | 2 - 16 x 25 side or 1 - 24 x 24 bottom return |
| Downflow | *0403A* | 2 - 10 x 20 or 1 - 14 x 25 top return |
| Downflow | *0603A* | 2 - 10 x 20 or 1 - 14 x 25 top return |
| Downflow | *0804B* | 2 - 14 x 20 or 1 - 16 x 25 top return |
| Downflow | *1005C* | 2 - 14 x 20 or 1 - 20 x 25 top return |
- Note 1: with a cooling unit over 4 tons use 2 - 16 x 25 filters on two side returns or a 20 x 25 on the bottom return.
- Upflow at 1800 CFM or more: use two side returns or one side plus bottom.
- Larger filters are fine; filters may also be in a central return.
- Horizontal installs: filters must be outside the furnace (central return).
- Filters are not supplied with the furnace; replace every two months or as needed.
Source: Goodman RS6612020r1 (GM9C96 service), Minimum Recommended Filter Size p.16-17
Models covered
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.