Goodman · Furnace
EE0 Lockout - too many ignition retries (3)
What the control is telling you
The control tried to light the burners 3 times and failed (no flame proven, or flame lost after lighting), so it locked out. The flowcharts call this code E0.
Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92
Likely causes
- Gas supply off or interrupted, gas valve switch OFF, or low inlet/manifold pressure
- Hot surface igniter not glowing, cracked or out of position
- Dirty or oxidized flame sensor / weak flame signal
- Vent or intake pipe blocked, too long, too many elbows or wrong termination; weak inducer
- 90% models: front cover (coil cover) pressure switch opening because the condensate trap or drain is blocked or not primed
- Poor ground or reversed line polarity (control cannot sense flame)
Test and repair steps
- Read the active code (Err menu) and the fault history (L6F menu) on the 7-segment display; cycle the thermostat to retry and watch the full sequence.
- Confirm the inducer starts and the igniter glows for the whole warm-up. No glow: check for 115 VAC at the igniter during warm-up - if voltage is there, replace the igniter.
- Igniter check (power off, igniter at 70-77 F): silicon nitride igniter should read 37-68 ohms. 80% models with the carbide mini igniter: 30-300 ohms.
- If the burners do not light gas valve switch ON, 24 VAC at the valve during trial for ignition, inlet pressure 4.5-10.0 in. w.c. natural gas / 11.0-13.0 in. w.c. LP with all appliances running.
- Check manifold pressure while firing natural gas high fire 3.2-3.8 in. w.c., LP 9.7-10.3 in. w.c. (see the Gas pressure table for each model).
- 90% models: make sure the front cover pressure switch stays closed - prime and clear the drain trap, check the switch hose for kinks or water, and check vent length, elbows and termination.
- If the burners light then drop out measure flame current with a DC microamp meter in series with the sensor - normal is 1 to 4 microamps. Clean the sensor with steel wool and check its position in the flame.
- Check grounding and polarity a reversed hot/neutral or a high-resistance neutral can cause flame-sense lockouts.
- Make sure manifold pressure stays steady during the run and does not drop below the range.
Settings for these units
Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat (single stage) | gH |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat (single stage) | gH |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
80 models in Goodman/Amana GM9S96/AM9S96, Goodman/Amana GM9S80/AM9S80, Goodman/Amana GM9C96/AM9C96
Other codes on the same units
- EE1 Pressure switch closed at start of heating cycle
- EE2 Pressure switch did not close (inducer runs, no ignition)
- EE3 High (primary) limit open
- EE4 Flame sensed with no call for heat
- EE5 Open fuse (short in low voltage wiring)
- EE6 Low flame signal
- EE8 High-stage pressure switch closed at start of heating cycle
- EE9 High-stage pressure switch did not close
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36; Error Codes (E0) flowchart p.51 (RS6612022r1), p.36 (RS6621008r2), p.39 (RS6612020r1); Checking Hot Surface Ignitor / Flame Sensor p.24-26. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.