EE9 High-stage pressure switch did not close
What the control is telling you
On a two-stage furnace the high-stage pressure switch does not close when the inducer goes to high speed. The furnace keeps running on low stage only. Flowcharts call this code E9.
Applies to: Goodman/Amana two-stage 96% furnaces GM9C96, GC9C96, AM9C96, AC9C96
Likely causes
- Pressure switch hose blocked, pinched or connected wrong
- Blocked flue or intake, or vent too long / too many elbows
- Blocked condensate drain
- Weak inducer on high speed
- Bad switch or loose wiring
Test and repair steps
- Inspect the high-stage pressure switch hose and repair or replace it.
- Check the flue and intake piping for blockage and for correct length, elbows and termination.
- Check the drain system and front cover pressure switch.
- With a manometer, compare the negative pressure at high inducer speed with the switch rating; enough vacuum but open switch = replace the switch.
- Check inducer voltage and amps; replace the inducer if it cannot pull enough vacuum.
- Tighten or correct the pressure switch wiring and retest a high-fire call.
Settings for these units
Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
| Configuration | Size code | Minimum filter |
|---|---|---|
| Upflow | *0403A* | 1 - 16 x 25 side or 1 - 14 x 24 bottom return |
| Upflow | *0603A* | 1 - 16 x 25 side or 14 x 24 bottom return |
| Upflow | *0603B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0803B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0804B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0804C* | 1 - 16 x 25 side or bottom return |
| Upflow | *0805C* | 1 - 16 x 25 side or bottom return (see note 1) |
| Upflow | *0805D* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return (see note 1) |
| Upflow | *1004C* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return |
| Upflow | *1005C* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return |
| Upflow | *1205D* | 2 - 16 x 25 side or 1 - 24 x 24 bottom return |
| Downflow | *0403A* | 2 - 10 x 20 or 1 - 14 x 25 top return |
Note 1: with a cooling unit over 4 tons use 2 - 16 x 25 filters on two side returns or a 20 x 25 on the bottom return.
Upflow at 1800 CFM or more: use two side returns or one side plus bottom.
Models that show this code
6 models in Goodman/Amana GM9C96/AM9C96
Other codes on the same units
- EE2 Pressure switch did not close (inducer runs, no ignition)
- EE3 High (primary) limit open
- EE4 Flame sensed with no call for heat
- EE5 Open fuse (short in low voltage wiring)
- EE6 Low flame signal
- EE8 High-stage pressure switch closed at start of heating cycle
- gH1 Gas heat, low stage
- gH2 Gas heat, high stage
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6612020r1 (GM9C96/GC9C96/AM9C96/AC9C96 service), 2 Stage Troubleshooting Codes, p.36; Error Code E1, E2 flowchart p.40. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.