gH2 Gas heat, high stage
What the display is showing
Shown while the two-stage furnace is heating on high fire. Normal operation during a call for heat.
Applies to: GM9C96/AM9C96 two-stage furnaces
Settings for these units
Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
| Configuration | Size code | Minimum filter |
|---|---|---|
| Upflow | *0403A* | 1 - 16 x 25 side or 1 - 14 x 24 bottom return |
| Upflow | *0603A* | 1 - 16 x 25 side or 14 x 24 bottom return |
| Upflow | *0603B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0803B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0804B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0804C* | 1 - 16 x 25 side or bottom return |
| Upflow | *0805C* | 1 - 16 x 25 side or bottom return (see note 1) |
| Upflow | *0805D* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return (see note 1) |
| Upflow | *1004C* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return |
| Upflow | *1005C* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return |
| Upflow | *1205D* | 2 - 16 x 25 side or 1 - 24 x 24 bottom return |
| Downflow | *0403A* | 2 - 10 x 20 or 1 - 14 x 25 top return |
Note 1: with a cooling unit over 4 tons use 2 - 16 x 25 filters on two side returns or a 20 x 25 on the bottom return.
Upflow at 1800 CFM or more: use two side returns or one side plus bottom.
Models that show this code
6 models in Goodman/Amana GM9C96/AM9C96
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: GM9C96 service RS6612020r1, 2 Stage Status Codes p.34. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.