Goodman · Furnace
EE8 High-stage pressure switch closed at start of heating cycle
What the control is telling you
On a two-stage furnace the high-stage pressure switch circuit is already closed at the start of a heat call. The furnace runs on low stage only (inducer still operates). Flowcharts call this code E8.
Applies to: Goodman/Amana two-stage 96% furnaces GM9C96, GC9C96, AM9C96, AC9C96
Likely causes
- High-stage pressure switch contacts stuck closed
- Short in the pressure switch circuit wiring
Test and repair steps
- Power off, remove the wires from the high-stage pressure switch and ohm the contacts with the inducer off - they must be open.
- Replace the high-stage pressure switch if the contacts are closed with no vacuum.
- If the switch is good, find and repair the short in the switch wiring.
- Retest a high-fire call (W1+W2) and confirm the furnace stages up.
Settings for these units
Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
| Configuration | Size code | Minimum filter |
|---|---|---|
| Upflow | *0403A* | 1 - 16 x 25 side or 1 - 14 x 24 bottom return |
| Upflow | *0603A* | 1 - 16 x 25 side or 14 x 24 bottom return |
| Upflow | *0603B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0803B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0804B* | 1 - 16 x 25 side or bottom return |
| Upflow | *0804C* | 1 - 16 x 25 side or bottom return |
| Upflow | *0805C* | 1 - 16 x 25 side or bottom return (see note 1) |
| Upflow | *0805D* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return (see note 1) |
| Upflow | *1004C* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return |
| Upflow | *1005C* | 2 - 16 x 25 side or 1 - 20 x 25 bottom return |
| Upflow | *1205D* | 2 - 16 x 25 side or 1 - 24 x 24 bottom return |
| Downflow | *0403A* | 2 - 10 x 20 or 1 - 14 x 25 top return |
Note 1: with a cooling unit over 4 tons use 2 - 16 x 25 filters on two side returns or a 20 x 25 on the bottom return.
Upflow at 1800 CFM or more: use two side returns or one side plus bottom.
Models that show this code
6 models in Goodman/Amana GM9C96/AM9C96
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6612020r1 (GM9C96/GC9C96/AM9C96/AC9C96 service), 2 Stage Troubleshooting Codes, p.36; Error Code E1, E2 flowchart p.40. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.