Goodman · Furnace
Eb5 Blower motor locked rotor
What the control is telling you
The motor failed to start 10 times in a row.
Applies to: GMVC96, GCVC96, AMVC96, ACVC96 (*BA, ComfortBridge)
Likely causes
- Something stuck in the blower housing
- Seized motor bearings
- Failed motor
Test and repair steps
- Turn off power before touching wiring or the board.
- Look in the blower housing for obstructions and clear them.
- If the wheel or motor is bad, replace it with the correct part.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
16 models in Goodman/Amana *MVC96 (34.5 in. chassis)
Other codes on the same units
- Eb1 Lost communication with blower motor
- Eb2 Blower motor hp does not match model data
- Eb3 Blower motor running in power, temperature or speed limit
- Eb4 Blower motor current trip or lost rotor control
- Eb6 Blower motor over/under voltage or over temperature
- Eb7 Blower motor missing parameters
- Eb9 Inadequate airflow
- Ec1 Network communication alarm
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman Service and Troubleshooting ACVC96*BA/AMVC96*BA/GCVC96*BA/GMVC96*BA , Alarm Code Table p.56 / Troubleshooting Chart p.63. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.