Goodman · Furnace

Eb9 Inadequate airflow

Medium severity Goodman/Amana *MVC96 (34.5 in. chassis)

What the control is telling you

Airflow is lower than what the control asks for. The furnace may run slow or stay on low stage when high stage is expected.

Applies to: GMVC96, GCVC96, AMVC96, ACVC96 (*BA, ComfortBridge)

Likely causes

  • Dirty filter
  • Restrictive or undersized ductwork

Test and repair steps

  1. Turn off power before touching wiring or the board.
  2. Check the filter. Clean or replace it.
  3. Check ducts for blockage and open all registers.
  4. Check duct size and fix or replace undersized duct.

Settings for these units

Models that show this code

16 models in Goodman/Amana *MVC96 (34.5 in. chassis)

*CVC960403BNB**CVC960603BNB**CVC960804CNB**CVC961005CNB**CVC961205DNB**MVC960403BNB**MVC960603BNB**MVC960803BNB**MVC960804CNB**MVC961005CNB**MVC961005DNB**MVC961205DNB*ACVC96AMVC96GCVC96GMVC96

Other codes on the same units

  • Eb4 Blower motor current trip or lost rotor control
  • Eb5 Blower motor locked rotor
  • Eb6 Blower motor over/under voltage or over temperature
  • Eb7 Blower motor missing parameters
  • Ec1 Network communication alarm
  • Ec2 E-module network communication alarm
  • Ec3 Bluetooth module network communication alarm
  • Ed0 No shared data on the network

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman Service and Troubleshooting ACVC96*BA/AMVC96*BA/GCVC96*BA/GMVC96*BA , Alarm Code Table p.56 / Troubleshooting Chart p.63. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.