Goodman · Furnace
Ed0 No shared data on the network
What the control is telling you
The control has no shared data loaded, so it does not know the furnace model settings. Load the data with a memory card or the phone app.
Applies to: GMVC96, GCVC96, AMVC96, ACVC96 (*BA, ComfortBridge)
Likely causes
- Shared data set was never loaded or was lost
Test and repair steps
- Turn off power before touching wiring or the board.
- Get the memory card made for this exact model.
- Insert the card before power is turned on. The card can come out after the data loads and power is cycled off.
- The error clears once the data is loaded. The CoolCloudHVAC app can also load shared data (card is the last resort).
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
16 models in Goodman/Amana *MVC96 (34.5 in. chassis)
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman Service and Troubleshooting ACVC96*BA/AMVC96*BA/GCVC96*BA/GMVC96*BA , Alarm Code Table p.56 / Troubleshooting Chart p.62. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.