Goodman · Furnace

Ed4 Memory card data rejected

Medium severity Goodman/Amana *MVC96 (34.5 in. chassis)

What the control is telling you

The control refused the shared data set loaded from the memory card, so the furnace may act oddly or not run.

Applies to: GMVC96, GCVC96, AMVC96, ACVC96 (*BA, ComfortBridge)

Likely causes

  • Shared data set does not match this furnace model

Test and repair steps

  1. Turn off power before touching wiring or the board.
  2. Confirm the card is the right one for this model and reload the data.
  3. Insert the card before power is on. Remove it only after the data loads and power is off.
  4. The error clears once the right data is loaded and power is cycled.

Settings for these units

Models that show this code

16 models in Goodman/Amana *MVC96 (34.5 in. chassis)

*CVC960403BNB**CVC960603BNB**CVC960804CNB**CVC961005CNB**CVC961205DNB**MVC960403BNB**MVC960603BNB**MVC960803BNB**MVC960804CNB**MVC961005CNB**MVC961005DNB**MVC961205DNB*ACVC96AMVC96GCVC96GMVC96

Other codes on the same units

  • Eb9 Inadequate airflow
  • Ec1 Network communication alarm
  • Ec2 E-module network communication alarm
  • Ec3 Bluetooth module network communication alarm
  • Ed0 No shared data on the network
  • Ed1 Invalid data on network
  • Ed5 Invalid downloaded firmware
  • Ed6 Unrecognized data ID

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman Service and Troubleshooting ACVC96*BA/AMVC96*BA/GCVC96*BA/GMVC96*BA , Alarm Code Table p.56 / Troubleshooting Chart p.62. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.