Goodman · Furnace

Eb3 Blower motor running in power, temperature or speed limit

Medium severity Goodman/Amana *MVC96 (34.5 in. chassis)

What the control is telling you

The motor is limiting itself, so airflow is lower than expected and the furnace runs with reduced performance.

Applies to: GMVC96, GCVC96, AMVC96, ACVC96 (*BA, ComfortBridge)

Likely causes

  • Dirty filter
  • Restrictive or undersized ductwork
  • High ambient temperature

Test and repair steps

  1. Turn off power before touching wiring or the board.
  2. Check the filter. Clean or replace it.
  3. Check ducts for blockage and make sure every register is fully open.
  4. Check duct size for the system and correct it if too small.

Settings for these units

Models that show this code

16 models in Goodman/Amana *MVC96 (34.5 in. chassis)

*CVC960403BNB**CVC960603BNB**CVC960804CNB**CVC961005CNB**CVC961205DNB**MVC960403BNB**MVC960603BNB**MVC960803BNB**MVC960804CNB**MVC961005CNB**MVC961005DNB**MVC961205DNB*ACVC96AMVC96GCVC96GMVC96

Other codes on the same units

  • E13 Redundant relay stuck closed
  • Eb0 Blower motor not running
  • Eb1 Lost communication with blower motor
  • Eb2 Blower motor hp does not match model data
  • Eb4 Blower motor current trip or lost rotor control
  • Eb5 Blower motor locked rotor
  • Eb6 Blower motor over/under voltage or over temperature
  • Eb7 Blower motor missing parameters

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman Service and Troubleshooting ACVC96*BA/AMVC96*BA/GCVC96*BA/GMVC96*BA , Alarm Code Table p.56 / Troubleshooting Chart p.63. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.