Goodman · Furnace

Eb0 Blower motor not running

High severity Goodman/Amana *MVC96 (34.5 in. chassis)

What the control is telling you

The control calls for the circulator blower but the motor is not running.

Applies to: GMVC96, GCVC96, AMVC96, ACVC96 (*BA, ComfortBridge)

Likely causes

  • Loose motor power leads or unplugged connector
  • Open circuit or loose wire at the inductor (3/4 hp and 1 hp models only)
  • Failed blower motor

Test and repair steps

  1. Turn off power before touching wiring or the board.
  2. Tighten the motor power connections.
  3. Check continuity through the inductor. Replace it if open or shorted.
  4. Check the motor. Replace it with the correct part if it is bad.

Settings for these units

Models that show this code

16 models in Goodman/Amana *MVC96 (34.5 in. chassis)

*CVC960403BNB**CVC960603BNB**CVC960804CNB**CVC961005CNB**CVC961205DNB**MVC960403BNB**MVC960603BNB**MVC960803BNB**MVC960804CNB**MVC961005CNB**MVC961005DNB**MVC961205DNB*ACVC96AMVC96GCVC96GMVC96

Other codes on the same units

  • E12 Redundant relay open
  • E13 Redundant relay stuck closed
  • Eb1 Lost communication with blower motor
  • Eb2 Blower motor hp does not match model data
  • Eb3 Blower motor running in power, temperature or speed limit
  • Eb4 Blower motor current trip or lost rotor control
  • Eb5 Blower motor locked rotor
  • Eb6 Blower motor over/under voltage or over temperature

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman Service and Troubleshooting ACVC96*BA/AMVC96*BA/GCVC96*BA/GMVC96*BA , Alarm Code Table p.56 / Troubleshooting Chart p.62. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.