Goodman · Furnace
Eb2 Blower motor hp does not match model data
What the control is telling you
The motor horsepower does not agree with the shared data in the control.
Applies to: GMVC96, GCVC96, AMVC96, ACVC96 (*BA, ComfortBridge)
Likely causes
- Wrong motor installed
- Wrong shared data set in the control
Test and repair steps
- Turn off power before touching wiring or the board.
- Confirm the motor hp matches the specified hp for the model.
- Check the shared data set is the right one. Reload it from the correct memory card if needed (card in before power on).
- The error clears once data and motor hp match.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
16 models in Goodman/Amana *MVC96 (34.5 in. chassis)
Other codes on the same units
- E12 Redundant relay open
- E13 Redundant relay stuck closed
- Eb0 Blower motor not running
- Eb1 Lost communication with blower motor
- Eb3 Blower motor running in power, temperature or speed limit
- Eb4 Blower motor current trip or lost rotor control
- Eb5 Blower motor locked rotor
- Eb6 Blower motor over/under voltage or over temperature
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman Service and Troubleshooting ACVC96*BA/AMVC96*BA/GCVC96*BA/GMVC96*BA , Alarm Code Table p.56 / Troubleshooting Chart p.63. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.