Goodman · Furnace
3 flashes Pressure switch stuck open
What the control is telling you
The inducer runs but the pressure switch never closes within 5 minutes, so the control goes into a 1-hour lockout. The inducer keeps running with no heat.
Applies to: GMES9, GCES9, AMES9, ACES9, VMES9, VCES9 (single stage, 92% and 96%)
Likely causes
- Pressure switch hose blocked, pinched or connected wrong
- Blocked flue or inlet air pipe, blocked drain, or weak inducer
- Wrong switch setpoint or bad contacts
- Loose or wrong wiring
Test and repair steps
- Turn off power before repairs.
- Inspect the switch hose and fix or replace it.
- Check flue and inlet piping for blockage, length, elbows and termination. Check the drain system.
- Correct the switch setpoint or contact movement, or replace the switch with the right part.
- Tighten or fix the wiring connection.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
57 models in Goodman/Amana *MES9 single-stage
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman Service and Troubleshooting GMES9*/GCES9*/AMES9*/ACES9*/VMES9*/VCES9* (RS6612016r3) , Troubleshooting Chart p.51; LED table p.44. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.