Goodman · Furnace

4 flashes Primary or auxiliary limit open

High severity Goodman/Amana *MES9 single-stage

What the control is telling you

A limit switch opened. The circulator blower runs and the furnace does not fire until the limit closes. Usually too little air over the heat exchanger.

Applies to: GMES9, GCES9, AMES9, ACES9, VMES9, VCES9 (single stage, 92% and 96%)

Likely causes

  • Failed primary or auxiliary limit
  • Dirty filter, restrictive ducts, wrong blower speed or failed blower
  • Loose wiring in the limit circuit

Test and repair steps

  1. Turn off power before repairs.
  2. Check the limits and replace if bad.
  3. Check filters and ductwork for blockage. Clean or clear them.
  4. Check blower speed and performance. Correct the speed or replace the blower.
  5. Tighten any loose wiring.

Settings for these units

Models that show this code

57 models in Goodman/Amana *MES9 single-stage

ACES96ACES960403BNAAACES960603BNAAACES960804CNAAACES961005CNAAACES961205DNAAAMES92AMES920403ANAAAMES920603BNAAAMES920803BNAAAMES920804CNAAAMES920805CNAAAMES921004CNAAAMES921005CNAAAMES921205DNAAAMES96AMES960403ANAAAMES960603BNAAAMES960803BNAAAMES960804CNAAAMES960805CNAAAMES961005CNAAAMES961205DNAAGCES96GCES960403BNAAGCES960603BNAAGCES960804CNAAGCES961005CNAAGCES961205DNAAGMES92GMES920403ANAAGMES920603BNAAGMES920803BNAAGMES920804CNAAGMES920805CNAAGMES921004CNAAGMES921005CNAAGMES921205DNAAGMES96GMES960403ANAAGMES960603BNAAGMES960803BNAAGMES960804CNAAGMES960805CNAAGMES961005CNAAGMES961205DNAAVCES96VCES960403BNAAVCES960603BNAAVCES960804CNAAVCES961005CNAAVMES96VMES960403ANAAVMES960603BNAAVMES960803BNAAVMES960804CNAAVMES961005CNAA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman Service and Troubleshooting GMES9*/GCES9*/AMES9*/ACES9*/VMES9*/VCES9* (RS6612016r3) , Troubleshooting Chart p.52; LED table p.44. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.