Goodman · Furnace

1 flash Lockout - three failed ignition tries

High severity Goodman/Amana *MES9 single-stage

What the control is telling you

The furnace made three ignition tries in one call for heat and never held a flame, so it locked out. The control resets itself after one hour.

Applies to: GMES9, GCES9, AMES9, ACES9, VMES9, VCES9 (single stage, 92% and 96%)

Likely causes

  • No gas reaching the burners
  • Front cover pressure switch open or its hose or wiring bad
  • Bad or misaligned igniter
  • Wrong orifices
  • Coated, oxidized or loosely connected flame sensor
  • Flame lost after lighting: gas supply interruption, lazy flames from wrong gas pressure or restricted flue or air piping, front cover pressure switch opening, weak inducer

Test and repair steps

  1. Turn off power before repairs.
  2. Find and fix any gas supply problem.
  3. Check the front cover pressure switch hose, wiring and contacts.
  4. Replace or realign the igniter. It breaks easily, so handle it with care.
  5. Check the flame signal. Sand or clean the sensor if it is coated.
  6. Check flue piping for blockage, length, elbows and termination. Check inducer performance.

Settings for these units

Models that show this code

57 models in Goodman/Amana *MES9 single-stage

ACES96ACES960403BNAAACES960603BNAAACES960804CNAAACES961005CNAAACES961205DNAAAMES92AMES920403ANAAAMES920603BNAAAMES920803BNAAAMES920804CNAAAMES920805CNAAAMES921004CNAAAMES921005CNAAAMES921205DNAAAMES96AMES960403ANAAAMES960603BNAAAMES960803BNAAAMES960804CNAAAMES960805CNAAAMES961005CNAAAMES961205DNAAGCES96GCES960403BNAAGCES960603BNAAGCES960804CNAAGCES961005CNAAGCES961205DNAAGMES92GMES920403ANAAGMES920603BNAAGMES920803BNAAGMES920804CNAAGMES920805CNAAGMES921004CNAAGMES921005CNAAGMES921205DNAAGMES96GMES960403ANAAGMES960603BNAAGMES960803BNAAGMES960804CNAAGMES960805CNAAGMES961005CNAAGMES961205DNAAVCES96VCES960403BNAAVCES960603BNAAVCES960804CNAAVCES961005CNAAVMES96VMES960403ANAAVMES960603BNAAVMES960803BNAAVMES960804CNAAVMES961005CNAA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman Service and Troubleshooting GMES9*/GCES9*/AMES9*/ACES9*/VMES9*/VCES9* (RS6612016r3) , Troubleshooting Chart p.51; LED table p.44. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.