Goodman · Furnace

Red LED 1 flash Red communications LED 1 flash - communication failure

Medium severity Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

What the control is telling you

The furnace control lost communication on the ComfortNet network.

Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces

Likely causes

  • Communication failure on the data lines
  • Bias / termination dip switches set wrong

Test and repair steps

  1. Press the learn button once quickly for a power-up reset.
  2. Check the bus BIAS and TERM dip switches are all ON.
  3. If a quick press does not clear it, hold the learn button for roughly 2 s (full factory-style network reset).

Settings for these units

Models that show this code

10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

GCVC90704CXGCVC90905DXGCVC91155DXGCVC950714CXGCVC950915DXGMVC950453BXGMVC950704CXGMVC950905CXGMVC950905DXGMVC951155DX

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Network Troubleshooting p.47. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.