Goodman · Furnace
Rx LED 1 steady flash Green receive LED single steady flash - no network found
What the control is telling you
The control is not finding a network.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Likely causes
- Broken or disconnected data wire(s)
- Furnace is wired as a legacy (24 V thermostat) system
Test and repair steps
- Safety turn power off before working on the control or wiring.
- Check the data 1 and data 2 wires and the terminal block connections.
- Twist stranded wires together before putting them in the terminal block.
- Confirm whether the furnace is meant to be legacy or communicating.
- Check the data 1 / data 2 voltages.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Other codes on the same units
- HI High-stage heat
- OP Normal - waiting for a call
- Red LED 1 flash Red communications LED 1 flash - communication failure
- Red LED 2 flashes Red communications LED 2 flashes - reset in progress
- Red LED off Red communications LED off - normal
- Rx LED off Green receive LED off - no power or communications error
- Rx LED on solid Green receive LED on solid - data lines miswired or shorted
- Rx LED rapid flash Green receive LED rapid flashing - normal network traffic
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Network Troubleshooting p.47. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.