Goodman · Furnace
Rapid flash Reversed polarity
What the control is telling you
The LED flashes rapidly all the time. 115 V or 24 V polarity is reversed, or the transformer's orange and gray wires are swapped. Furnace will not run.
Applies to: GMES9, GCES9, AMES9, ACES9, VMES9, VCES9 (single stage, 92% and 96%)
Likely causes
- 115 V hot and neutral swapped at the furnace or control
- Orange and gray transformer wires reversed
- Poor unit ground
Test and repair steps
- Turn off power before repairs.
- Check the wiring diagram and correct the 115 V polarity.
- Swap the orange and gray wires at the transformer if they are reversed.
- Check the unit ground and correct it.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
57 models in Goodman/Amana *MES9 single-stage
Other codes on the same units
- 7 flashes Low flame signal
- 8 flashes Igniter relay fault
- 9 flashes Twinning fault
- 10 flashes Open fuse - no 24 V at the control
- 11 flashes Igniter open
- 12 flashes Inducer relay fault
- LED off No LED - no power or control failure
- LED steady on Normal operation
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman Service and Troubleshooting GMES9*/GCES9*/AMES9*/ACES9*/VMES9*/VCES9* (RS6612016r3) , Troubleshooting Chart p.53; LED table p.44. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.