Goodman · Furnace

12 flashes Inducer relay fault

High severity Goodman/Amana *MES9 single-stage

What the control is telling you

Problem in the inducer circuit or its relay on the control. Furnace will not run.

Applies to: GMES9, GCES9, AMES9, ACES9, VMES9, VCES9 (single stage, 92% and 96%)

Likely causes

  • Inducer wiring loose
  • Bad inducer
  • Poor unit ground
  • Faulty control
  • Blockage in the inducer or vent

Test and repair steps

  1. Turn off power before repairs.
  2. Check and fix the wiring from the control to the inducer.
  3. Check for blockage in the inducer and vent. Replace the inducer if bad.
  4. Check the unit ground wire. Replace the control if it is faulty.

Settings for these units

Models that show this code

57 models in Goodman/Amana *MES9 single-stage

ACES96ACES960403BNAAACES960603BNAAACES960804CNAAACES961005CNAAACES961205DNAAAMES92AMES920403ANAAAMES920603BNAAAMES920803BNAAAMES920804CNAAAMES920805CNAAAMES921004CNAAAMES921005CNAAAMES921205DNAAAMES96AMES960403ANAAAMES960603BNAAAMES960803BNAAAMES960804CNAAAMES960805CNAAAMES961005CNAAAMES961205DNAAGCES96GCES960403BNAAGCES960603BNAAGCES960804CNAAGCES961005CNAAGCES961205DNAAGMES92GMES920403ANAAGMES920603BNAAGMES920803BNAAGMES920804CNAAGMES920805CNAAGMES921004CNAAGMES921005CNAAGMES921205DNAAGMES96GMES960403ANAAGMES960603BNAAGMES960803BNAAGMES960804CNAAGMES960805CNAAGMES961005CNAAGMES961205DNAAVCES96VCES960403BNAAVCES960603BNAAVCES960804CNAAVCES961005CNAAVMES96VMES960403ANAAVMES960603BNAAVMES960803BNAAVMES960804CNAAVMES961005CNAA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman Service and Troubleshooting GMES9*/GCES9*/AMES9*/ACES9*/VMES9*/VCES9* (RS6612016r3) , Troubleshooting Chart p.53; LED table p.44. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.