Goodman · Furnace
b7 Blower motor missing parameters
What the control is telling you
The motor does not have enough data to run properly, or it failed to start 40 times in a row. Furnace will not run. ComfortNet thermostat shows MOTOR PARAMS b7.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Likely causes
- Problem with the furnace control or its shared data
- Locked rotor
Test and repair steps
- Safety turn power off before working on the control or wiring.
- Check the control has the correct shared data for this model (see d0 / d4). Reload with the correct memory card if needed.
- Check for a locked rotor (see b5).
- Replace failed parts with the correct replacements.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.