Goodman · Furnace

b9 Low indoor airflow

Medium severity Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

What the control is telling you

Airflow is lower than the control is asking for. The furnace may run with reduced performance or stay on low stage when high stage is called.

Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces

Likely causes

  • Dirty filter
  • Restricted ductwork
  • Undersized ductwork

Test and repair steps

  1. Check and clean or replace the filter.
  2. Check ducts for blockage and open all registers.
  3. If the ducts are undersized for the system, they need to be resized.

Settings for these units

Models that show this code

10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

GCVC90704CXGCVC90905DXGCVC91155DXGCVC950714CXGCVC950915DXGMVC950453BXGMVC950704CXGMVC950905CXGMVC950905DXGMVC951155DX

Other codes on the same units

  • b4 Blower motor trip (lost rotor control or high current)
  • b5 Blower motor locked rotor
  • b6 Blower motor over/under voltage or over temperature
  • b7 Blower motor missing parameters
  • C1 Low-stage cooling
  • C2 High-stage cooling
  • d0 No shared data on the control
  • d4 Memory card data rejected

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.57. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.