Goodman · Furnace

d0 No shared data on the control

High severity Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

What the control is telling you

The control has no model data (shared data) loaded, so the furnace will not run. ComfortNet thermostat shows NO NET DATA d0.

Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces

Likely causes

  • Shared data never loaded (often after a control replacement)

Test and repair steps

  1. Safety turn power off before working on the control or wiring.
  2. Get the memory card for this exact model.
  3. Power off, plug the card in, then turn the power on. Data loads at power-up.
  4. Turn the power off again before you pull the card out.
  5. The code clears once the data is loaded.

Settings for these units

Models that show this code

10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

GCVC90704CXGCVC90905DXGCVC91155DXGCVC950714CXGCVC950915DXGMVC950453BXGMVC950704CXGMVC950905CXGMVC950905DXGMVC951155DX

Other codes on the same units

  • b6 Blower motor over/under voltage or over temperature
  • b7 Blower motor missing parameters
  • b9 Low indoor airflow
  • C1 Low-stage cooling
  • C2 High-stage cooling
  • d4 Memory card data rejected
  • E0 Lockout - ignition failed 3 times
  • E1 Low-stage pressure switch closed at start of heat

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.53-57. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.