Goodman · Furnace

E1 Low-stage pressure switch closed at start of heat

Medium severity Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

What the control is telling you

At the start of a heat call the low-stage pressure switch is already closed before the inducer runs. The furnace will not start. ComfortNet thermostat shows PS1 CLOSED E1.

Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces

Likely causes

  • Low-stage pressure switch contacts stuck
  • Short in the pressure switch wiring

Test and repair steps

  1. Safety turn power off before working on the control or wiring.
  2. Pull the wires off the low-stage switch and check it with a meter with the inducer off. It should be open.
  3. If it reads closed, replace it with the correct part.
  4. If the switch is open, look for a short in the harness to the switch and repair it.

Settings for these units

Models that show this code

10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

GCVC90704CXGCVC90905DXGCVC91155DXGCVC950714CXGCVC950915DXGMVC950453BXGMVC950704CXGMVC950905CXGMVC950905DXGMVC951155DX

Other codes on the same units

  • d0 No shared data on the control
  • d4 Memory card data rejected
  • E0 Lockout - ignition failed 3 times
  • E2 Low-stage pressure switch will not close
  • E3 High limit or rollout limit open
  • E4 Flame sensed with no call for heat
  • E5 Control fuse open
  • E6 Low flame signal

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.53-57. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.