Goodman · Furnace
E1 Low-stage pressure switch closed at start of heat
What the control is telling you
At the start of a heat call the low-stage pressure switch is already closed before the inducer runs. The furnace will not start. ComfortNet thermostat shows PS1 CLOSED E1.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Likely causes
- Low-stage pressure switch contacts stuck
- Short in the pressure switch wiring
Test and repair steps
- Safety turn power off before working on the control or wiring.
- Pull the wires off the low-stage switch and check it with a meter with the inducer off. It should be open.
- If it reads closed, replace it with the correct part.
- If the switch is open, look for a short in the harness to the switch and repair it.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.53-57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.