Goodman · Furnace
E5 Control fuse open
What the control is telling you
The 3 A fuse on the control board is blown, usually from a short in the 24 V wiring. A ComfortNet thermostat runs on battery power and shows Battery Power.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Likely causes
- Short in the low voltage wiring (thermostat, outdoor unit, accessories)
Test and repair steps
- Safety turn power off before working on the control or wiring.
- Find the short in the 24 V wiring first: thermostat cable, outdoor unit wires, humidifier or other add-ons.
- Replace the fuse with a 3 A automotive type fuse only.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Other codes on the same units
- E1 Low-stage pressure switch closed at start of heat
- E2 Low-stage pressure switch will not close
- E3 High limit or rollout limit open
- E4 Flame sensed with no call for heat
- E6 Low flame signal
- E7 Igniter circuit fault
- E8 High-stage pressure switch closed at start of heat
- E9 High-stage pressure switch will not close
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.53-57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.