Goodman · Furnace
E9 High-stage pressure switch will not close
What the control is telling you
On a call for high heat the high-stage pressure switch does not close. The furnace keeps running on low stage only.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Likely causes
- Pressure switch hose blocked, pinched or on the wrong port
- Blocked vent or intake pipe
- Blocked drain
- Weak inducer
- Wrong switch set point or bad switch
- Loose or wrong wiring
Test and repair steps
- Safety turn power off before working on the control or wiring.
- Check the switch hose and taps.
- Check the vent and intake pipes for blockage, length, elbows and termination.
- Check the drain trap and lines.
- Check inducer performance.
- Check the wiring, then replace the switch or inducer with the correct part if needed.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.53-57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.