Goodman · Furnace
E4 Flame sensed with no call for heat
What the control is telling you
The control sees flame when the gas valve should be closed. Inducer and blower both keep running. ComfortNet thermostat shows IMPROPER FLAME E4.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Likely causes
- Flame sensor or its wire shorted to ground
- Burner flame lingering after shutdown
- Gas valve slow to close
Test and repair steps
- Safety gas work by a licensed gas technician only. Shut the gas off before opening any gas fitting.
- Look at the burners after the call ends. If flame stays, shut the gas off at the manual valve.
- Check the flame sensor and its wire for a short to ground and fix it.
- If flame lingers or the valve closes slowly, replace the gas valve.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.53-57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.