Goodman · Furnace
E7 Igniter circuit fault
What the control is telling you
The control found a problem in the igniter circuit. Furnace will not run. ComfortNet thermostat shows IGNITER FAULT E7.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Likely causes
- Igniter wiring loose or wrong
- Shorted igniter
- Poor unit ground
- Igniter relay failed on the control
Test and repair steps
- Safety turn power off before working on the control or wiring.
- Check the wiring from the control to the igniter.
- Check the igniter resistance. Replace a shorted igniter with the correct part.
- Check the furnace ground wiring.
- If wiring, igniter and ground are good, check for igniter voltage from the control. No output = replace the control.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Other codes on the same units
- E1 Low-stage pressure switch closed at start of heat
- E2 Low-stage pressure switch will not close
- E3 High limit or rollout limit open
- E4 Flame sensed with no call for heat
- E5 Control fuse open
- E6 Low flame signal
- E8 High-stage pressure switch closed at start of heat
- E9 High-stage pressure switch will not close
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.53-57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.