Goodman · Furnace

E2 Low-stage pressure switch will not close

High severity Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

What the control is telling you

The inducer runs but the low-stage pressure switch never closes, so there is no ignition. The inducer may keep running. ComfortNet thermostat shows PS1 OPEN E2.

Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces

Likely causes

  • Pressure switch hose blocked, pinched or on the wrong port
  • Blocked vent or intake pipe
  • Blocked condensate drain
  • Weak inducer
  • Wrong switch set point or bad switch
  • Loose or wrong wiring

Test and repair steps

  1. Safety turn power off before working on the control or wiring.
  2. Check the switch hose for water, kinks and cracks and that it is on the right tap.
  3. Check the vent and intake pipes for blockage, length, elbows and termination.
  4. Check the drain trap and drain lines. A plugged drain will hold the switch open.
  5. Check the inducer runs at full speed with no noise or wobble.
  6. Check the wiring at the switch. Replace the switch or inducer only with the correct parts.

Settings for these units

Models that show this code

10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

GCVC90704CXGCVC90905DXGCVC91155DXGCVC950714CXGCVC950915DXGMVC950453BXGMVC950704CXGMVC950905CXGMVC950905DXGMVC951155DX

Other codes on the same units

  • d0 No shared data on the control
  • d4 Memory card data rejected
  • E0 Lockout - ignition failed 3 times
  • E1 Low-stage pressure switch closed at start of heat
  • E3 High limit or rollout limit open
  • E4 Flame sensed with no call for heat
  • E5 Control fuse open
  • E6 Low flame signal

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.53-57. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.