What the control is telling you
The primary limit, auxiliary limit or a rollout limit is open. The blower keeps running and the burners stay off. ComfortNet thermostat shows HIGH LIMIT OPEN E3.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Likely causes
- Low airflow over the heat exchanger: dirty filter, restricted ducts, wrong blower speed, failed blower motor
- Flame rollout from misaligned burners, a blocked vent or intake, or a failed inducer
- Loose or wrong wiring
Test and repair steps
- Safety turn power off before working on the control or wiring.
- Check the filter and duct system first. Clean or replace the filter and open any closed registers.
- Check the blower speed setting and motor. Temperature rise must be inside the rating plate range.
- Rollout limits are manual reset. If one tripped, find out why before you reset it: check burner alignment, vent and intake pipes, and the inducer.
- The auxiliary limits near the blower are also manual reset.
- Tighten or fix any loose limit wiring.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.53-57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.