Goodman · Furnace

E3 High limit or rollout limit open

High severity Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

What the control is telling you

The primary limit, auxiliary limit or a rollout limit is open. The blower keeps running and the burners stay off. ComfortNet thermostat shows HIGH LIMIT OPEN E3.

Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces

Likely causes

  • Low airflow over the heat exchanger: dirty filter, restricted ducts, wrong blower speed, failed blower motor
  • Flame rollout from misaligned burners, a blocked vent or intake, or a failed inducer
  • Loose or wrong wiring

Test and repair steps

  1. Safety turn power off before working on the control or wiring.
  2. Check the filter and duct system first. Clean or replace the filter and open any closed registers.
  3. Check the blower speed setting and motor. Temperature rise must be inside the rating plate range.
  4. Rollout limits are manual reset. If one tripped, find out why before you reset it: check burner alignment, vent and intake pipes, and the inducer.
  5. The auxiliary limits near the blower are also manual reset.
  6. Tighten or fix any loose limit wiring.

Settings for these units

Models that show this code

10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet

GCVC90704CXGCVC90905DXGCVC91155DXGCVC950714CXGCVC950915DXGMVC950453BXGMVC950704CXGMVC950905CXGMVC950905DXGMVC951155DX

Other codes on the same units

  • d4 Memory card data rejected
  • E0 Lockout - ignition failed 3 times
  • E1 Low-stage pressure switch closed at start of heat
  • E2 Low-stage pressure switch will not close
  • E4 Flame sensed with no call for heat
  • E5 Control fuse open
  • E6 Low flame signal
  • E7 Igniter circuit fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.53-57. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.