Goodman · Furnace
b5 Blower motor locked rotor
What the control is telling you
The blower motor failed to start 10 times in a row. Furnace will not run. ComfortNet thermostat shows MTR LCKD ROTOR b5.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
Likely causes
- Something jamming the blower wheel
- Seized motor bearings
- Failed blower motor
Test and repair steps
- Safety turn power off before working on the control or wiring.
- Spin the blower wheel by hand and look for anything in the housing.
- Repair or replace the wheel or motor if it is stuck or rubbing.
- If it spins freely, check the motor shaft turns and replace the motor if needed.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
10 models in Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
Other codes on the same units
- b1 Lost communication with blower motor
- b2 Blower motor size does not match model data
- b3 Blower motor limiting (power, temperature or speed)
- b4 Blower motor trip (lost rotor control or high current)
- b6 Blower motor over/under voltage or over temperature
- b7 Blower motor missing parameters
- b9 Low indoor airflow
- C1 Low-stage cooling
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Troubleshooting Chart p.57. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.