Goodman · Furnace
EEb External gas valve error - valve not energized when it should be
What the control is telling you
During a heat call the control does not see voltage at the gas valve when it should. Flowcharts call this code Eb. Note: the wiring diagram legend labels this code 'Internal Gas Valve Error' while the troubleshooting chart and flowchart say external (valve not powered) - follow the chart.
Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92
Likely causes
- Miswired or loose gas valve harness
- Gas valve coil shorted to ground
- Open front cover pressure switch on 90% models (it is in series with the valve)
- Failed control board output
Test and repair steps
- Check the gas valve wiring against the wiring diagram and correct any miswiring.
- Remove the wires from the gas valve and check the valve for a short to ground; replace a shorted valve.
- With a call for heat and the igniter on, check for 24 VAC between the valve wires (MV/MVL and common) at the harness connector on the control board.
- Voltage at the board but not at the valve: check the harness and, on 90% models, the front cover pressure switch in series with the valve.
- No voltage at the board output during trial for ignition: replace the integrated control board.
- If the valve voltage does not match transformer voltage, look for a grounding problem.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36; Error Code (Eb & EC) flowchart p.38 (RS6621008r2); wiring diagram legend p.53 (RS6612022r1). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.