Weil-McLain boiler error codes
61 codes (51 faults, 10 normal display and menu codes).
| Code | Meaning | Severity / type |
|---|---|---|
| L1 POLARITY | Line voltage polarity reversed | Medium |
| AIR PRESSURE SW FAULT | Air pressure switch input open | Medium |
| AUTO LIMIT | Auto-reset limit circuit open | Medium |
| BLOWER FAULT | Blower speed fault | High |
| BOILER OUT OPEN | Boiler outlet sensor open circuit | High |
| BOILER OUT SHORT | Boiler outlet sensor shorted | High |
| BURNER ON | Burner on status | Normal status |
| CH | Central heat call active | Normal status |
| CH VOLTAGE HIGH | Too much voltage on the CH / Thermostat 1 input | Medium |
| CONFIG MISMATCH | Stored configuration does not match the harness | High |
| CONFIGURATION | Control board not configured | High |
| DHW | Domestic hot water call active | Normal status |
| DHW VOLTAGE HIGH | Too much voltage on the DHW / Thermostat 2 input | Medium |
| DISPLAY COMM | Display communication lost | Low |
| EXP BOARD COM FAULT | Expansion board to U-Control communication fault | Medium |
| FALSE FLAME | Flame sensed when the gas valve is off | Critical |
| FAULT L1 POLARITY | Line 1 polarity reversed | High |
| FAULT MANUAL LIMIT | Manual limit fault | High |
| FLAME FAULT | Flame detected when no flame should exist | High |
| FLAME LOST | Flame lost while running | High |
| FLUE TEMP TOO HIGH | Flue gas temperature too high | High |
| GAS PRESSURE SW FAULT | Gas pressure switch open | Medium |
| GAS VALVE FAULT | Gas valve output circuit fault | High |
| GV FAULT EXPANSION BRD | Expansion board gas valve output fault | Medium |
| HARDWARE FAULT 1 | Control board hardware fault 1 | High |
| HARDWARE FAULT 2 | Control board hardware fault 2 | High |
| HARDWARE FAULT 3 | Control board hardware fault 3 | High |
| HARDWARE FAULT 4 | Control board hardware fault 4 | High |
| HARDWARE FAULT 5 | Pilot valve output fault (board or harness short) | High |
| HARDWARE FAULT 6 | Control board hardware fault 6 | High |
| HARDWARE FAULT 7 | Main valve output fault (board or harness short) | High |
| HARDWARE FAULT 8 | Control board hardware fault 8 | High |
| HIGH TEMP LIMIT | High temperature limit reached | High |
| HW FAULT EXPANSION BRD | Expansion control board hardware fault | Low |
| IGNITION FAULT | No flame after 5 ignition attempts | High |
| LIMIT OPEN | External limit open | High |
| LOW WTR CUTOFF OPEN | Low water cutoff contacts open | High |
| LWCO | Low water cutoff active / LWCO test | High |
| LWCO GREEN | Low water cutoff indicator green | Normal status |
| LWCO RED | Low water cutoff indicator red | High |
| MANUAL LIMIT | Manual-reset limit circuit open (includes rollout switch) | Critical |
| NO DISPLAY - BOILER RUNNING | Display blank while boiler is operating | Low |
| NO DISPLAY - NO 120V | No display and no boiler components running, no 120V power | High |
| NO DISPLAY - NO 24V | No display, no 24V control power | Medium |
| RETURN > SUPPLY | Return temperature above supply | Low |
| SPILL SWITCH | Spill switch open (flue gas spilling at the draft hood) | Critical |
| STANDBY | Standby display | Normal status |
| SUPPLY 58F > RETURN | Supply temperature far above return | Medium |
| SUPPLY 58° F > RETURN | Supply exceeds return by 58°F | Medium |
| SUPPLY WATER TEMPERATURE TOO HIGH | Supply temperature above 200°F while burner runs | High |
| Software Incompatible | Main control and display software mismatch | Medium |
| Supply 60F > Return | Supply more than 60F above return (soft lockout) | High |
| System Return > Supply | System return hotter than system supply | Medium |
| TEMP RISE TOO QUICKLY | Supply water temperature rising too fast | High |
| TEMPERATURE SENSOR | Temperature sensor short, open, or readings disagree | Medium |
| TEMPERATURE SENSOR FAULT | Temperature sensor shorted or open | Medium |
| Target Reduced - Boiler | Target reduced because boiler outlet is near max temperature | Normal status |
| Target Reduced - Flow | Target reduced for low water flow across heat exchanger | Normal status |
| Target Reduced - Flue | Target reduced for high flue temperature | Normal status |
| Unconfigured Net 1 or Net 2 Demand | Net 1 or Net 2 input active but not configured | Normal status |
| Virtual Input Active | Modbus commanding a virtual TT input | Normal status |
Models covered
ECO Tec 110ECO Tec 150ECO Tec 199ECO Tec 80
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.