Weil-McLain boiler error codes

61 codes (51 faults, 10 normal display and menu codes).

CodeMeaningSeverity / type
L1 POLARITYLine voltage polarity reversedMedium
AIR PRESSURE SW FAULTAir pressure switch input openMedium
AUTO LIMITAuto-reset limit circuit openMedium
BLOWER FAULTBlower speed faultHigh
BOILER OUT OPENBoiler outlet sensor open circuitHigh
BOILER OUT SHORTBoiler outlet sensor shortedHigh
BURNER ONBurner on statusNormal status
CHCentral heat call activeNormal status
CH VOLTAGE HIGHToo much voltage on the CH / Thermostat 1 inputMedium
CONFIG MISMATCHStored configuration does not match the harnessHigh
CONFIGURATIONControl board not configuredHigh
DHWDomestic hot water call activeNormal status
DHW VOLTAGE HIGHToo much voltage on the DHW / Thermostat 2 inputMedium
DISPLAY COMMDisplay communication lostLow
EXP BOARD COM FAULTExpansion board to U-Control communication faultMedium
FALSE FLAMEFlame sensed when the gas valve is offCritical
FAULT L1 POLARITYLine 1 polarity reversedHigh
FAULT MANUAL LIMITManual limit faultHigh
FLAME FAULTFlame detected when no flame should existHigh
FLAME LOSTFlame lost while runningHigh
FLUE TEMP TOO HIGHFlue gas temperature too highHigh
GAS PRESSURE SW FAULTGas pressure switch openMedium
GAS VALVE FAULTGas valve output circuit faultHigh
GV FAULT EXPANSION BRDExpansion board gas valve output faultMedium
HARDWARE FAULT 1Control board hardware fault 1High
HARDWARE FAULT 2Control board hardware fault 2High
HARDWARE FAULT 3Control board hardware fault 3High
HARDWARE FAULT 4Control board hardware fault 4High
HARDWARE FAULT 5Pilot valve output fault (board or harness short)High
HARDWARE FAULT 6Control board hardware fault 6High
HARDWARE FAULT 7Main valve output fault (board or harness short)High
HARDWARE FAULT 8Control board hardware fault 8High
HIGH TEMP LIMITHigh temperature limit reachedHigh
HW FAULT EXPANSION BRDExpansion control board hardware faultLow
IGNITION FAULTNo flame after 5 ignition attemptsHigh
LIMIT OPENExternal limit openHigh
LOW WTR CUTOFF OPENLow water cutoff contacts openHigh
LWCOLow water cutoff active / LWCO testHigh
LWCO GREENLow water cutoff indicator greenNormal status
LWCO REDLow water cutoff indicator redHigh
MANUAL LIMITManual-reset limit circuit open (includes rollout switch)Critical
NO DISPLAY - BOILER RUNNINGDisplay blank while boiler is operatingLow
NO DISPLAY - NO 120VNo display and no boiler components running, no 120V powerHigh
NO DISPLAY - NO 24VNo display, no 24V control powerMedium
RETURN > SUPPLYReturn temperature above supplyLow
SPILL SWITCHSpill switch open (flue gas spilling at the draft hood)Critical
STANDBYStandby displayNormal status
SUPPLY 58F > RETURNSupply temperature far above returnMedium
SUPPLY 58° F > RETURNSupply exceeds return by 58°FMedium
SUPPLY WATER TEMPERATURE TOO HIGHSupply temperature above 200°F while burner runsHigh
Software IncompatibleMain control and display software mismatchMedium
Supply 60F > ReturnSupply more than 60F above return (soft lockout)High
System Return > SupplySystem return hotter than system supplyMedium
TEMP RISE TOO QUICKLYSupply water temperature rising too fastHigh
TEMPERATURE SENSORTemperature sensor short, open, or readings disagreeMedium
TEMPERATURE SENSOR FAULTTemperature sensor shorted or openMedium
Target Reduced - BoilerTarget reduced because boiler outlet is near max temperatureNormal status
Target Reduced - FlowTarget reduced for low water flow across heat exchangerNormal status
Target Reduced - FlueTarget reduced for high flue temperatureNormal status
Unconfigured Net 1 or Net 2 DemandNet 1 or Net 2 input active but not configuredNormal status
Virtual Input ActiveModbus commanding a virtual TT inputNormal status

Models covered

ECO Tec 110ECO Tec 150ECO Tec 199ECO Tec 80

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.