Weil-McLain · Boiler

HARDWARE FAULT 5 Pilot valve output fault (board or harness short)

High severity Weil-McLain CGa Series 4

What the control is telling you

The board sees voltage on the pilot valve output when it should not. Could be the board or a pilot valve harness shorted to 24 VAC.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

Likely causes

  • Pilot valve harness shorted to 24 VAC
  • Control board failure

Test and repair steps

  1. Turn off power to the boiler before unplugging connectors or measuring resistance. Restore power only for the voltage check.
  2. Unplug the pilot valve harness at P12 and check for voltage on harness C12 pin 4.
  3. Voltage there find and fix the short in the harness.
  4. No voltage plug everything back in and cycle power. If it comes back at the end of the next heat cycle, replace the control.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.66. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.