Weil-McLain · Boiler
FLAME LOST Flame lost while running
What the control is telling you
The pilot flame signal dropped out during a burn.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
Likely causes
- Weak flame signal: dirty/corroded flame rod or bad sense wire
- Inlet or manifold gas pressure dropping at high or low fire
Test and repair steps
- Gas work is for a gas-qualified tech only. Leak-test every fitting you open.
- Check the pilot flame signal in the control Diagnostics (under 60 needed for proven flame per the manual).
- No signal check the flame sense wire and flame rod for continuity and corrosion. Replace if needed.
- Measure inlet and manifold pressure at high fire and at reduced fire. Both must stay inside the manual's ranges.
Other codes on the same units
- CONFIGURATION Control board not configured
- DHW VOLTAGE HIGH Too much voltage on the DHW / Thermostat 2 input
- FALSE FLAME Flame sensed when the gas valve is off
- HARDWARE FAULT 1 Control board hardware fault 1
- HARDWARE FAULT 2 Control board hardware fault 2
- HARDWARE FAULT 3 Control board hardware fault 3
- HARDWARE FAULT 4 Control board hardware fault 4
- HARDWARE FAULT 5 Pilot valve output fault (board or harness short)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.66. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.