Weil-McLain · Boiler

FALSE FLAME Flame sensed when the gas valve is off

Critical severity Weil-McLain CGa Series 4

What the control is telling you

The control sees a flame signal while it is not powering the pilot or main valves.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

Likely causes

  • Pilot valve or a main gas valve not closing (leaking through)
  • Gas valve wiring wrong

Test and repair steps

  1. Gas work is for a gas-qualified tech only. Leak-test every fitting you open.
  2. Look at the pilot and burners. If there is a flame, close the manual gas ball valves and make sure the flame goes out.
  3. Check the pilot valve and both main valve wires against the wiring diagram. Fix any wiring error and do a full start-up check.
  4. Wiring is right check that the pilot valve and both main valves actually stop the gas. Replace any valve that leaks through.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.65. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.