Weil-McLain · Boiler
CONFIG MISMATCH Stored configuration does not match the harness
What the control is telling you
The configuration number saved in the board is different from the number the board reads from the model harness.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
Likely causes
- Control swapped from another boiler
- Bad model harness or loose P13 connector
- Faulty control board
Test and repair steps
- Look at line 2 of the display CGa natural gas should be 15, CGa propane 5.
- If the number shown for the boiler is right, press Enter.
- If it is wrong, check 24 VAC at P13 (natural gas: pins 2, 3, 4 and 5; propane: pins 3 and 5). Press Enter once the right number shows.
- Voltages are correct at P13 but the model still reads wrong: replace the control.
- Never put the boiler back in service until the configuration matches the boiler.
Other codes on the same units
- L1 POLARITY Line voltage polarity reversed
- AUTO LIMIT Auto-reset limit circuit open
- BOILER OUT OPEN Boiler outlet sensor open circuit
- BOILER OUT SHORT Boiler outlet sensor shorted
- CH VOLTAGE HIGH Too much voltage on the CH / Thermostat 1 input
- CONFIGURATION Control board not configured
- DHW VOLTAGE HIGH Too much voltage on the DHW / Thermostat 2 input
- FALSE FLAME Flame sensed when the gas valve is off
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.64. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.